40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log  Not logged in ELOG logo
Entry  Fri Nov 4 18:31:05 2016, Lydia, Update, CDS, c1auxex channels/pins for Acromag 
    Reply  Sat Nov 5 15:45:44 2016, rana, Update, CDS, c1auxex channels/pins for Acromag 
       Reply  Mon Nov 7 19:49:44 2016, Johannes, Update, CDS, acromag chassis hooked up to PSL acromag_chassis_location.jpgacromag_chassis_top_view.jpg
          Reply  Tue Nov 8 17:51:09 2016, Lydia, Update, CDS, acromag chassis hooked up to PSL 
             Reply  Mon Nov 21 19:54:13 2016, Johannes, Update, CDS, acromag chassis hooked up to PSL acromag_chassis.jpg
                Reply  Wed Nov 30 11:56:56 2016, Lydia, Update, CDS, Wiring for Acromag auxex replacement auxex_acromag.pdf
                   Reply  Wed Nov 30 14:54:01 2016, Johannes, Update, CDS, Slow machine replacement 
                      Reply  Wed Dec 14 19:16:57 2016, Lydia, Update, CDS, Acromag Binary I/O testing 
                         Reply  Tue Jan 31 22:15:02 2017, Johannes, Update, CDS, vme crate backplane adapter boards vme_backplane_conn_sketch.jpg
                            Reply  Tue Feb 7 19:14:59 2017, Johannes, Update, CDS, vme crate backplane adapter board layout vme_backplane.pdf
                               Reply  Wed Feb 15 00:26:44 2017, Johannes, Update, DAQ, panels and pcbs acromag_chassis_panel.pdfvme_backplane_panel.pdfrfAmp.pdf
                                  Reply  Wed Feb 15 09:06:13 2017, ericq, Update, DAQ, panels and pcbs 
                                     Reply  Wed Feb 15 22:21:12 2017, Lydia, Update, DAQ, panels and pcbs 
Message ID: 12632     Entry time: Mon Nov 21 19:54:13 2016     In reply to: 12607     Reply to this: 12649
Author: Johannes 
Type: Update 
Category: CDS 
Subject: acromag chassis hooked up to PSL 

[Lydia, Johannes]

We connected and powered up the Acromag chassis today. It lives in 1X4 and is powered by the Sorensen +20V power supply in 1X5 via the fuse rail on the side of 1X4. For this we had to branch off the 20V path to the dewhitening and anti-image filter crate of the c1:susaux driven SOS optics. After confirming that none of the daughter modules in the crate draw from the 20V line, we added a wire leading to a new fuse we added for this unit and ran a power cable from there.

The diagnostic connector of the PSL laser is now connected to the unit and a tmux session was created on megatron that interfaces with the chassis and broadcasts the EPICS channels. We need to watch out in the coming days for epics freezes/outages, as in the past these seemed to occur around the same times we were toying with the Acromags.

Quote:

We set up the chassis in 1X7 today. Steve is ordering a longer 25 pin cable to reach. Until then the PSL diagnostic channels will not be usable.

 

Attachment 1: acromag_chassis.jpg  1.820 MB  | Hide | Hide all
acromag_chassis.jpg