Wed Jun 8 13:50:39 2016, jamie, Configuration, CDS, Spectracom IRIG-B card installed on fb1
|
Thu Jun 9 13:28:07 2016, jamie, Configuration, CDS, Spectracom IRIG-B card installed on fb1
|
Fri Jun 10 12:09:01 2016, jamie, Configuration, CDS, IRIG-B debugging
|
Fri Jun 10 12:21:54 2016, jamie, Configuration, CDS, GPS receiver not resetting properly
|
Mon Jun 20 11:11:20 2016, Steve, Configuration, CDS, GPS receiver not resetting properly
|
Mon Jun 20 11:19:41 2016, jamie, Configuration, CDS, GPS receiver not resetting properly
|
Mon Jun 20 14:03:04 2016, jamie, Configuration, CDS, EndRun GPS receiver upgraded, fixed
|
Wed Jun 15 10:19:10 2016, Steve, Configuration, CDS, GPS antennas... debugging 6x
|
|
Message ID: 12158
Entry time: Wed Jun 8 13:50:39 2016
Reply to this: 12161
|
Author: |
jamie |
Type: |
Configuration |
Category: |
CDS |
Subject: |
Spectracom IRIG-B card installed on fb1 |
|
|
[EDIT: corrected name of installed card]
We just installed a Spectracom TSyc-PCIe timing card on fb1. The hope is that this will help with the GPS timeing syncronization issues we've been seeing in the new daqd on fb1, hopefully elliminating some of the potential failure channels.
The driver, called "symmetricom" in the advLigoRTS source (name of product from competing vendor), was built/installed (from DCC T1500227):
controls@fb1:~/rtscore/tests/advLigoRTS-40m 0$ cd src/drv/symmetricom/
controls@fb1:~/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom 0$ ls
Makefile stest.c symmetricom.c symmetricom.h
controls@fb1:~/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom 0$ make
make -C /lib/modules/3.2.0-4-amd64/build SUBDIRS=/home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom modules
make[1]: Entering directory `/usr/src/linux-headers-3.2.0-4-amd64'
CC [M] /home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom/symmetricom.o
/home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom/symmetricom.c:59:9: warning: initialization from incompatible pointer type [enabled by default]
/home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom/symmetricom.c:59:9: warning: (near initialization for ‘symmetricom_fops.unlocked_ioctl’) [enabled by default]
/home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom/symmetricom.c: In function ‘get_cur_time’:
/home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom/symmetricom.c:89:2: warning: ISO C90 forbids mixed declarations and code [-Wdeclaration-after-statement]
/home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom/symmetricom.c: In function ‘symmetricom_init’:
/home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom/symmetricom.c:188:2: warning: ISO C90 forbids mixed declarations and code [-Wdeclaration-after-statement]
/home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom/symmetricom.c:222:3: warning: label ‘out_remove_proc_entry’ defined but not used [-Wunused-label]
/home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom/symmetricom.c:158:22: warning: unused variable ‘pci_io_addr’ [-Wunused-variable]
/home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom/symmetricom.c:156:6: warning: unused variable ‘i’ [-Wunused-variable]
Building modules, stage 2.
MODPOST 1 modules
CC /home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom/symmetricom.mod.o
LD [M] /home/controls/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom/symmetricom.ko
make[1]: Leaving directory `/usr/src/linux-headers-3.2.0-4-amd64'
controls@fb1:~/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom 0$ sudo make install
#remove all old versions of the driver
find /lib/modules/3.2.0-4-amd64 -name symmetricom.ko -exec rm -f {} \; || true
find /lib/modules/3.2.0-4-amd64 -name symmetricom.ko.gz -exec rm -f {} \; || true
# Install new driver
install -D -m 644 symmetricom.ko /lib/modules/3.2.0-4-amd64/extra/symmetricom.ko
/sbin/depmod -a || true
/sbin/modprobe symmetricom
if [ -e /dev/symmetricom ] ; then \
rm -f /dev/symmetricom ; \
fi
mknod /dev/symmetricom c `grep symmetricom /proc/devices|awk '{print $1}'` 0
chown controls /dev/symmetricom
controls@fb1:~/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom 0$ ls /dev/symmetricom
/dev/symmetricom
controls@fb1:~/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom 0$ ls -al /dev/symmetricom
crw-r--r-- 1 controls root 250, 0 Jun 8 13:42 /dev/symmetricom
controls@fb1:~/rtscore/tests/advLigoRTS-40m/src/drv/symmetricom 0$
|