40m QIL Cryo_Lab CTN SUS_Lab TCS_Lab OMC_Lab CRIME_Lab FEA ENG_Labs OptContFac Mariner WBEEShop
  40m Log  Not logged in ELOG logo
Entry  Fri Sep 23 16:25:01 2011, steve, Update, VAC, vac rack UPS battery replaced P1080252.JPGP1080254.JPG
    Reply  Fri Mar 27 10:38:40 2015, steve, Update, VAC, vac rack UPS battery replaced UPSvac.jpg
       Reply  Tue Mar 1 09:37:15 2016, steve, Update, VAC, vac rack UPS batteries replaced vacRackBat.jpg
Message ID: 12014     Entry time: Tue Mar 1 09:37:15 2016     In reply to: 11178
Author: steve 
Type: Update 
Category: VAC 
Subject: vac rack UPS batteries replaced 

Amstron batteries replaced after 11 months with SP-12-5.5HR,  2 years warranty from replaceUPSbattery.com

Quote:

Batteries replaced after 3.5 years with Amstron AP-1250F2,  8x 12V 6Ah

Quote:

APC Smart -UPS 2200   model: SUA2200RM2U   batteries were replaced by compatible RBC43, 8x  12V5A

 

Note: the replace battery LED did not go out ( well pasted 24 hrs ) till the self test bottom was hold down for 2-3 sec

Attachment 1: vacRackBat.jpg  205 kB  | Hide | Hide all
vacRackBat.jpg