Entry  Wed Apr 15 15:14:18 2015, ericq, Update, Computer Scripts / Programs, CDSutils upgraded to v474 
    Reply  Wed Apr 15 20:54:18 2015, Jenne, Update, Computer Scripts / Programs, CDSutils upgrade bad 
       Reply  Wed Apr 15 23:29:08 2015, Jenne, Update, Computer Scripts / Programs, CDSutils upgrade undone 
          Reply  Thu Apr 23 21:05:23 2015, rana, Update, Computer Scripts / Programs, CDSutils upgrade undone 
Message ID: 11223     Entry time: Wed Apr 15 23:29:08 2015     In reply to: 11221     Reply to this: 11240
Author: Jenne 
Type: Update 
Category: Computer Scripts / Programs 
Subject: CDSutils upgrade undone 

Q remotely reverted this change.  Scripts seem to work again.

Quote:

The SUS align/misalign scripts don't work after the new CDS utils upgrade. 

I don't know if it's looking for the _SWSTAT channel to confirm that the offset has been turned on/off, or if it is trying to set that channel, to do the switching, but either way, the script is failing.  Recall that our version of the RCG still has _SW1R and _SW2R, rather than the newer _SWSTAT for the filter banks. 

ezca.ezca.EzcaConnectError: Could not connect to channel (timeout=2s): C1:SUS-PRM_OL_PIT_SWSTAT

Q, can you please (please, please, pretty please) undo this upgrade, and then hold off on any further changes to the system for a few weeks?

 